How to set up Dead band for Co2?

Organicpoop

Well-Known Member
I have a trollmaster hydro pro x. I injected at 800 ppm and the system and computer shut off and no gas leaks. then the PPM kept going up to 2900PPM.
I was told this is a dead band setting.

I have no idea what that is nor where to set it.
 

Attachments

Organicpoop

Well-Known Member
Thought so and I put on lowest setting on the dial of the Triton injector. Grow store said its dead band on my computer and I don't even have my head around the idea, other then that time I took LSD at a famous "Dead band" show in Eugene Oregon. Guy whips out a freaking 5 gallon carboy of Liquid LSD and I mistakenly walked in and he saud, "Hay were kinda busy man" rubber gloves up to their arms and full face masks.
 

Lordhooha

Well-Known Member
Thought so and I put on lowest setting on the dial of the Triton injector. Grow store said its dead band on my computer and I don't even have my head around the idea, other then that time I took LSD at a famous "Dead band" show in Eugene Oregon. Guy whips out a freaking 5 gallon carboy of Liquid LSD and I mistakenly walked in and he saud, "Hay were kinda busy man" rubber gloves up to their arms and full face masks.
The injection on the triton is completely separate. The deadband is right on your screen I set mine for +/-200 it’ll allow it to ramp up over my set point by 200 ppm and wont kick on until it’s below 200ppm of my set point. Sounds like your rooms are really well seal. Also what is your set point on the hydro x currently? Not the dead band. I’m betting it’s set for 2800 or 2850 which would make since that it gets up to 2900ppm.
 