I need to cool down my basement and am thinking of running 15 feet of ducting to the drier vent and the drier vent is 5 foot to outside (20 feet total)... Will a 400cfm inline fan be able to do push this air 20 feet total??
Yes,keep in mind every 90= about 5' of straight pipe.So now 20' of pipe with 3 90's is 35' ish.So limit the turns or use chunks of stretched hose to make longer corners.
Yeah gonna run the 6" ducting to my 4" drier vent, don't think it should be a problem... What's the farthest I could run this venting with a 400CFM inline fan??
I've had this one for 30+ years. It pops up an opens when any air is blow through. Seals good but you better have a good fan. And it needs painted or at least the ones from 30 years ago do.
I went from a 4" 33cfm inline fan to a 4" 195 cfm in line fan. Cut fan on time in a 24hr period from 16 hours to 3.5 hrs. Needs a muffler and I had to put the dampener on or it never got to the 84F setpoint due to convection.