I came up with a cheap and simple way to test the throughput of an inline fan, so I could see how my carbon filter and ductwork affected it. It's definitely not too precise, but way better than nothing. And the results were surprising.
The basic idea: Take a large garbage bag, tape up the mouth around a small cylinder of cardboard (so you can fit it over the end of the fan), and time how long it takes to fill.
For example, I have a 55 gallon trash bag. That's 7.35 cubic feet (found that online). I took an S&P TD100 (4 inch) inline fan, which is rated at 100 CFM, and timed how long it took to fill the bag. (This is a very imprecise measurement -- when is the bag "full"?) I did this 4 times and averaged the results: 4.85 seconds. The math is then 7.35 / 4.85 (to get cubic feet per second) x 60 (to convert to cubic feet per minute). This is:
7.35 x 60 / 4.85 = 91 CFM
So I measured the fan at 91 CFM. It's rated at 100 CFM, so I am at least in the right ballpark.
I'll skip the calculations for the rest of my measurements and just give the results.
Exhausting through about 8 feet of 4 inch insulated duct, with a 90 degree bend: 65 CFM.
I have a homemade carbon filter. The carbon is packed into the wide end of a 6" to 4" reducer. My first attempt had 2" of carbon, which is about 2 lbs. (So a cylinder of carbon with a diameter of 6 inches, 2 inches deep.) It has a prefilter made of a thin layer of polyester quilt batting. With the filter (but not the ductwork): 21 CFM.
Wow. So I cut the carbon in half -- same as before, but with 1 inch of carbon (about 1 lb): 26 CFM.
I never did check with both the ductwork and the filter -- it seemed clear it wasn't going to be enough (I have a 56 cubic foot tent and am looking for an air change every 3 minutes, which is about 19 CFM).
So I returned the TD100 and bought a TD100X, which is rated at 135 CFM. I put it into use right away, so never did get a measurement of the fan on its own. But here are the measurements I have:
With the 1 inch carbon filter described above and an S&P backdraft damper: 24 CFM
...as above with about 90 inches of 6 inch insulated ductwork on the exhaust side, with a 90 degree bend: 22 CFM
...as above with about 80 inches of 4 inch insulated ductwork between the carbin filter and the fan, with a 90 degree bend: 22 CFM
...and lastly, as above but without the backdraft damper: 30 CFM.
I think the S&P fans are known to be "weak" -- dropping off fast with increases of static pressure, and a true centrifugal fan would probably behave very differently.
Anyway, figured I'd throw this out there in case it helps anyone else.
The basic idea: Take a large garbage bag, tape up the mouth around a small cylinder of cardboard (so you can fit it over the end of the fan), and time how long it takes to fill.
For example, I have a 55 gallon trash bag. That's 7.35 cubic feet (found that online). I took an S&P TD100 (4 inch) inline fan, which is rated at 100 CFM, and timed how long it took to fill the bag. (This is a very imprecise measurement -- when is the bag "full"?) I did this 4 times and averaged the results: 4.85 seconds. The math is then 7.35 / 4.85 (to get cubic feet per second) x 60 (to convert to cubic feet per minute). This is:
7.35 x 60 / 4.85 = 91 CFM
So I measured the fan at 91 CFM. It's rated at 100 CFM, so I am at least in the right ballpark.
I'll skip the calculations for the rest of my measurements and just give the results.
Exhausting through about 8 feet of 4 inch insulated duct, with a 90 degree bend: 65 CFM.
I have a homemade carbon filter. The carbon is packed into the wide end of a 6" to 4" reducer. My first attempt had 2" of carbon, which is about 2 lbs. (So a cylinder of carbon with a diameter of 6 inches, 2 inches deep.) It has a prefilter made of a thin layer of polyester quilt batting. With the filter (but not the ductwork): 21 CFM.
Wow. So I cut the carbon in half -- same as before, but with 1 inch of carbon (about 1 lb): 26 CFM.
I never did check with both the ductwork and the filter -- it seemed clear it wasn't going to be enough (I have a 56 cubic foot tent and am looking for an air change every 3 minutes, which is about 19 CFM).
So I returned the TD100 and bought a TD100X, which is rated at 135 CFM. I put it into use right away, so never did get a measurement of the fan on its own. But here are the measurements I have:
With the 1 inch carbon filter described above and an S&P backdraft damper: 24 CFM
...as above with about 90 inches of 6 inch insulated ductwork on the exhaust side, with a 90 degree bend: 22 CFM
...as above with about 80 inches of 4 inch insulated ductwork between the carbin filter and the fan, with a 90 degree bend: 22 CFM
...and lastly, as above but without the backdraft damper: 30 CFM.
I think the S&P fans are known to be "weak" -- dropping off fast with increases of static pressure, and a true centrifugal fan would probably behave very differently.
Anyway, figured I'd throw this out there in case it helps anyone else.