Any Electricical Advice (no I wont hold any one responsible)

SWIMoryou

Active Member
Have a 15 AMP and a 20 amp breaker each with a sigle 12/2 w/ground running to my room. Will this be enough to run

1 70 Watt HPS
1 50 Watt MH
8 42 watt CFLs
4 40 Watt T-12s
2 8" Cooling Fans
4 4" cooling fans

ANd which should I place on what circut

I was planning on placing the MH and the 8 CFLS on the 15 amp and the HPS and the T-12's on the 20 effectively having a dedicated breaker for each of the seperate rooms vegging and flowering vegging on the 15 flowering on the 20

will this be safe?
 

TeaTreeOil

Well-Known Member
You can run all of that on a single circuit. Assuming the fans are just fans and not air conditioners.

What else you can run on it.... you have about 2400 watts per 20 amp branch.
 

SWIMoryou

Active Member
You can run all of that on a single circuit. Assuming the fans are just fans and not air conditioners.

What else you can run on it.... you have about 2400 watts per 20 amp branch.
well already got the 2 so cant be too safe and having seperate bnreakers for vege and flower room is fine with me

Thank you for the advice and the wonderfull quioting of the electrical load for a 20 amp circut
 