Originally Posted by kambone 2-1000 ballasts 240v
1-vortex fan 120v
1-room ac 120v
1-eb n grow 120v
1-fish tank aerator 120v
These item all to run from a 50amp breaker on main inside service panel
to a sub panel containing 1-30 amp breaker/1 -20 amp breaker.
Currently, i need wiring info as far as correct gauge to account for
14 hours of use. THX! purely newbee 2 so all help is greatly appreciated. |
??? You are going to pull one leg of the 240V from the 30a breaker and the other leg from the 20a breaker for the 2 1000W lights?
It will work, but *seriously* doubt that would pass code.
I'd run (if using a sub panel)
1 15a 240V breaker (lights take about 9a)
1 15A 120V for the AC
1 15A 120V for the rest.
Why does everyone want a sub panel?